HomeMy WebLinkAboutIFB 2025291-01 - UPS Backup Center Addendum 1The Liebert EXM UPS provides efficient and economical operation with a flexible power system offering scalable and redundant features that is optimized to meet the unique demands of midsize IT and critical power applications. An intuitive, customizable touchscreen control panel provides Status At A Glance information and multiple levels of user security. Matching ancillary cabinets provide the ability to meet specific demands for run time, bypass and parallel requirements.
Touch Screen Display Modular Design
Best in Class Efficiency
Option 1: Liebert 3-phase UPS- eXm 15kVa UPS with integrated Maintenance Bypass cabinet.
Liebert EXM Single Module UPS System each consisting of the following: One (1) 15kVA Nameplate Liebert EXM UPS, model 47SA015BACH20CX, with the following features:
•System Input Voltage of 208/120V, 3 Phase, 4 wire plus ground
•System Output Voltage of 208/120V, 3 Phase, 4 wire plus ground
•15kVA Scalable to 15kVA UPS System
•208V Native Output Voltage
•Single Input Configuration
•One (1) IntelliSlot Unity Dual Protocol Card; P/N: IS-UNITY-DP; Monitoring and configuration ofVertiv products and environmental sensors through stand-alone Web UI or integration with
IFB 2025291-01 UPS Backup System Addendum 1
Liebert Expandable UPS System UPS Optional Redundant/Expansion Module is
available
Trellis™, Liebert Nform, LIFE™ Services. Supports third-party management systems using SNMP, Modbus or BACnet.
•Transformer-Free Architecture - Efficiency up to 95% in double conversion mode
•Unity Power Factor Rating - Delivers more usable power per kVA
•Load Power Factor Support - Supports loads 0.5 lagging to unity without derating
•Energy Optimization Mode (Eco-Mode)
•65kAIC Rating - Provides interrupting rating and labeling of 65kA
•Active Power Factor Corrected IGBT Input Converter
•PWM transistorized (IGBT) inverter
•Continuous Duty Static Bypass Switch
•Input Contacts - Dry contacts are available for functions including monitoring external breakers,on-generator signal, and other functions
•Output Contacts - Dry contacts are available for functions including a permissive signal tomaintenance bypass SKRU, to trip external breakers, and other functions
•Generator Load Control - Suppresses battery charging reducing power demand by an externalsignal. Shifts unit from Eco Mode to double conversion (if applicable), and synchronizes theinverter output with the bypass
•Automatic retransfer - Provides return to inverter power after an overload
•DSP based controls - Provides digital control of power conversion and system operation
•Backlit LCD display - Monitors power conversion, UPS operation and utility conditions. Deviationsare logged for troubleshooting
•Temperature-Compensated Charging/Battery Load Test
•Top-and-bottom-entry cable access
•Front only service access
•Local Emergency Power Off (EPO)
•LIFE™ Services for the 1st year
•IP 20 enclosure
•Casters and leveling feet
•UL and cUL Listed to UL Standard 1778 5th Edition
•20 min @ 15 kVA, 1 x Internal String of ENERSYS 1-HX150E-FR Batteries (Preferred)
•21 min: Run Time at Ordered KVA
The solution includes One (1) Maintenance Bypass Cabinet(s), model 47MBB32CC0L11BD with the following features:
•3 Switching Devices (BIB,MBB,MIB)
•70 Amp Breaker Trip Rating
•Key Interlock (SKRU)
•Cabinet Mounted Left Attached to Module with connecting cables factory supplied
•200 MM - 7.9 inches Frame Size
•Top or Side Access required for MBC Installation.
•Front Access service design
Quantity Part Number Description
1 47SA015BACH20CX Main Unit
1 47MBB32CC0L11BD MBC/BDC Unit